C.M. Heating is one of the leading providers of air conditioning repair and air conditioning service in Everett, WA, offering timely solutions to problems related to your air conditioning system. Our HVAC technicians will come to your rescue when you want emergency AC service or repair, or just need a hand with your residential or commercial cooling problems.

You'll find we take our job seriously and highly value the trust that is placed in us. C.M. Heating goes far beyond what others do by investing in the training and equipment necessary to protect your home or family in Everett, WA. Whether you have a central AC system, Heat Pump or Ductless Mini Split we are here to help.


CM Heating installed a Rheem 13 SEER 3ton AC for this customer on 2/6/17, and now the unit is having issues cooling the upstairs portion. The customer will set the home for 71 degrees and the downstairs portion will cool to that temperature relatively quickly, however, the upstairs portion is considerably warmer than downstairs. Customer would like to have it checked out, I believe there may be some bedrooms upstairs, so that could be pretty inconvenient. Upon investigation, The TXV sensing bulb wasn’t secured to the suction line correctly see pic for details. I fix by properly securing sensing bulb wrapping it in insulation zip tieing the insulation and wrapping it in tape. Not charging customer at this time. Customer was interested in signing up for HVAC club membership sending them the price to sign up. Alll operations normal at this time.

Everett, WA
08-15-2018


Customer stated that the Bryant AC system stopped working. Homeowner advised that the compressor was recently replaced. System was operational upon arrival. I checked pressures and they were off. I checked indoor coil and found frosting up. Thermostat is sending proper air flow speed, air flow is not the issue. TXV was not properly regulating refrigerant and is causing the suction line to ice up to the compressor despite sensing bulb fully seated against suction line. TXV will need to be replaced. No other issues at this time.

Everett, WA
08-14-2018


Customer says that their air conditioner was not cooling, they thought maybe it needed refrigerant. Upon diagnosis the technician found a leak in the coil system.

Everett, WA
08-31-2018


Customer says that their air conditioner was not cooling, they thought maybe it needed refrigerant. Upon diagnosis the technician found a leak in the coil system.

Everett, WA
08-31-2018


CM Heating performed prepaid maintenance's on the fireplace, furnace and AC units in home. Customer on monthly gfp and heat and cool clubs. Fireplace in good working condition. Cleaned and tested Furnace in good working condition. Cleaned tested. Filter. Ac working well at this time. Amp draws and dual cap good. Everything clean and working properly.

Everett, WA
03-21-2019


Customer stated that their heat pump was not working. Performed diagnostic test on non working heat pump. Bad dual run capacitor, replaced with new. All operations normal at this time.

Everett, WA
07-19-2018


Customer noticed they had very low air flow on their air conditioning unit and that it was taking a long time to cool. Their unit was installed approximately one year ago. Customer has variable speed blower motor and was concerned with weak air flow and equipment running for long longer duration then his last heating equipment. had 112 supply temp and 68 return 42 delta T all checked out great explained to customer how the variable speed blowers work with longer run times with lower amp draws for more efficient run times. Air flow check out normal. All operations normal at this time.

Everett, WA
07-03-2018


Customer stated that their AC would not turn on and they believed the unit was frozen. Upon investigation, the technician found that the control board is faulty. On a call for cool, no signal is being sent by the board to activate the condenser and fan but the board is still able to send a signal for a call for heat. Verified this by jumping the R to Y terminal (nothing happened) R to G (delayed start) R to W (unit began cycle of operation for heat). Replacement of board is needed for further diagnostic

Everett, WA
06-26-2018


Customer stated that their AC would not turn on and they believed the unit was frozen. Upon investigation, the technician found that the control board is faulty. On a call for cool, no signal is being sent by the board to activate the condenser and fan but the board is still able to send a signal for a call for heat. Verified this by jumping the R to Y terminal (nothing happened) R to G (delayed start) R to W (unit began cycle of operation for heat). Replacement of board is needed for further diagnostic

Everett, WA
06-26-2018


CM Heating Perform maintenance on a gas furnace, ac, hot water heater. All system operating normally.

Everett, WA
04-26-2019


CM Heating performed an air conditioner diagnostic and found crossed wires on thermostat to control board. As well as performed a routine maintenance on the unit, tested capacitor and compressor and fan motor. We Cleaned inside and out and tested temperature drop and system is running at this time.

Everett, WA
05-14-2019


CM heated performed a maintenance on an AC and gas Furnace. Tune and clean gas furnace. Removed and cleaned the burners and flame sensor. Tested the capacitor, gas pressure and igniter. Took amp draws of motors. Visually inspected the control board and blower assembly. Cleaned filters and checked delta t. Inducer motor house is cracked. Igniter is testing high resistance. Tune and clean ac. Tested capacitor, contactor, pressures, delta t and amp draws. System is running at this time. Recommend replacing furnace due to age. Recommend changing filter to 4in paper pleat due to dust getting past the current filter.

everett, WA
05-14-2019


CM Heating Performed a preventive maintenance service on Gas Furnace, hot water tank, and heat pump. -Checked and ensure all safety components are within manufacturers requirements and working properly. -Measured -/+ tolerance on consumable components. -Inspected mechanical and electrical devices/parts within the unit. -Refrigerant pressure verified. -Inspected tank for leaks and flush the system. Tank does not have an expansion tank. All operations normal at this time.

Everett, WA
04-24-2019


CM Heating Performed maintenance on ac system.

Everett, WA
04-05-2019


CM Heating performed maintenance on furnace (GF), Hot water Tank (HWT), and Heat pump/Air conditioner (HP/AC). GF Maintenance - System is running well, all components are within manufacturer’s specifications and in good working order. EAC has been pulled and cleaned, furnace vacuumed. No issues at this time. HWT Maintenance - Tank has been flushed and inspected for any leaks (gas/water). All in good working order, no issues. HP/AC Maintenance - All components are within manufacturer’s specifications and are in good working condition. Tested only in heat mode due to temperature outside but performance in heating is great. No issues at this time.

Everett, WA
04-15-2019